CANLON brand MBP Pro Pre-applied Waterproofing Membrane, composed of white polymer sheet (HDPE or TPO), pressure sensitive adhesive and weather resistant granular layer on the upper surface, is specifically developed to elevate the construction and application performance of below grade waterproofing. Designed with an adhesive selvedge on one side,and a layer of back-coated selvedge on the other side, it realizes an adhesive to adhesive bond on selvedge overlaps, which enhances the installation applicability and significantly improves the overlapping strength. Even in harsh jobsite condition (such as rains, water, low temperature, etc.), it still achieves effective connection between membranes.
Applied either horizontally to smoothly prepared concrete substrate and compacted earth or crushed stone substrate; or vertically to permanent formwork. Concrete is then cast directly against the adhesive side of the membranes.
MBP Pro Pre-applied Waterproofing Membrane is used for the waterproofing of exterior basement walls, foundations, floor plates, etc.The same product is suitable for vertical and horizontal areas and usable against pressurized water.·White sheet with non-recycled HDPE or TPO(pellets) as raw materials --easy to identify whether or not add inferior recycled materials .
·Resistant to weather conditions--the specially formulated surface coating ensures that self-adhesive properties withstand up to 49 days of UV exposure, rain water, dirt and contaminants, etc.
·Good dimensional stability-- dimensional variation rate does not exceed 0.5%, with smaller wrinkles comparing to similar products.
·Resistant against impact and puncture, effectively reduces the possibility of membrane being destroyed during construction.
·High resistance to chemicals such as acid, alkali and salt, protect the membranes in most areas of alkaline land or acid rain.
·MBP Pro Pre-applied Waterproofing Membranes unaffected by wet jobsite conditions--effective overlapping can be realized in the water.
Substrate Preparation
The surface must be sound, even, stable and clean with no protrusions, gaps, joints or voids greater than 10 mm. To prevent movements of penetrations such as pipe penetrations for water and electricity during concrete pour and membrane installation, they have to be fixed and stabilized. Damaged concrete should be renovated with MBP Multi Mortar and sharp edges be removed first.
Material- horizontal application
MBP-Pro Pre-applied Waterproofing Membrane must be placed with weather resistant coating layer facing the concrete pour and the white polymer sheet facing the substrate.The overlapping between the membranes is 75 mm. Before removing the plastic release liner (on adhesive selvedge) ensure that the membrane's overlapping selvedge is positioned correctly and the underside of the succeeding sheet clean prior to overlapping.
Then start removing of plastic release liner to bond the membranes together. Use a heavy roller to ensure a complete perfect bonding between the membranes. Then go ahead with removing of plastic release liner and press membranes together.
Material-vertical application
MBP-Pro Pre-applied Waterproofing Membrane must be fixed mechanically to the substrate by using fixing tools. These fixings must have a low profile head so that the membrane won't be damaged from the fixings.The overlapping between the membranes is 75 mm. Before removing the plastic release liner (on adhesive selvedge) ensure that the membrane's overlapping selvedge is positioned correctly and the underside of the succeeding sheet clean prior to overlapping.
Then start removing of plastic release liner to bond the membranes together. Use a heavy roller to ensure a complete perfect bonding between the membranes. Then go ahead with removing of plastic release liner and press membranes together.
End laps overlapping
For butt joint of end laps, apply MST Detail Strip centered over center of the butt joint with the adhesive surface facing up and roll firmly. For overlapping the end laps, apply MST Double Side Tape centered over the edge of the overlap and ensure the tape be rolled firmly.
Repairs before concrete placement
In case of damaging the MBP-Pro Membrane during installation of formwork and reinforcement steel placement, repair damage by applying the MST Sanded Tape centered over the damaged area prior to the concrete pour. Apply PUS Polyurethane Sealant for sealing around penetrations, joint processing such as expansion joint.
Pouring of concrete
Ensure that all overlapping areas are sealed and the release liner is removed in that area. Do not damage the membrane during pouring of concrete.
Formwork removal
It is very important not to remove formwork until the concrete has sufficient compressive strength to develop the required adhesion with MBP-Pro Membrane.Too early removal of all formworks can lead to a displacement of MBP Pro Pre-applied Waterproofing Membrane or concrete damage. A minimum concrete compressive strength of 10N/mm2 recommended prior to removing formwork.
NO. | Property | Value | Test method | |
1 | Thickness/mm | ≥1.2 | EN 1849-2:2019 | |
2 | Tensile strengthN/50mm | Longitudinal | ≥600 | EN12311-2:2013 |
Transversal | ≥600 | |||
3 | Elongation at rupture(%) | Longitudinal | ≥500 | EN12311-2:2013 |
Transversal | ≥500 | |||
4 | Resistance to tearing/N | Longitudinal | ≥250 | EN12310-2:2018 |
Transversal | ≥250 | |||
5 | Shear Resistance of Joints(N/50mm) | ≥300 | EN 12317-2:2010 | |
6 | Resistance to static loading | 20kg, no leakage | EN12730:2015 | |
7 | Resistance to impact/mm | 1500 | EN12691:2018 | |
8 | Water-tightness | There is no pressure drop during the test | EN 1928:2000 | |
9 | Durability against Aging | There is no pressure drop during the test | EN1926:2000 | |
EN1847:2009 | ||||
10 | Durability against Chemicals | There is no pressure drop during the test | EN1928:2000 | |
EN1847:2009 | ||||
11 | Reaction to Fire | Class E | EN13501-1+A1:2009 | |
Remark:All the test items according to EN Standard. |